EDA9015 Analog measurement module
Category:
Intelligent I/O module
Key words:
Product description
Main feature
● EDA9015 analog measurement module can measure: 12 voltage or current。
● EDA9015 module can be widely used in various industrial control and measurement systems。It can measure the true RMS of AC or DC 0 ~ 250V voltage or 0 ~ 200mA current signal。
● Communication interface is RS-485 interface, power supply is DC8 ~ 24V, communication protocol is MOSBUS-RTU, ASCII code, hexadecimal LC-02 protocol 3 configurable options
● Input: 12 channels 0 ~ 250V voltage。Input signal is DC or AC (frequency 25 ~ 75Hz)。The range can be: 100mV, 1V, 5V, 10V, 60V, 100V, 250V。
● or 12 channels 0 ~ 200mA current。Input signal is DC or AC (frequency 25 ~ 75Hz)。The range can be: 1mA, 10mA, 20mA, 100mA, 200mA。
● 1.2 times the range can be correctly measured;Overload 2x range input 1s is not damaged。Isolation: Isolation between signal input and communication interface output, isolation voltage 1000V DC。DATA+, DATA-, VCC, and GND are the output terminals and the GND terminals are on the same ground
● 0.Level 2 accuracy
Product function
● Input signal
Input: 12 channels 0 to 250V voltage。Input signal is DC or AC (frequency 25 ~ 75Hz)。The range can be: 100mV, 1V, 5V, 10V, 60V, 100V, 250V。Or 12 channels 0 ~ 200mA current。Input signal is DC or AC (frequency 25 ~ 75Hz)。The range can be: 1mA, 10mA, 20mA, 100mA, 200mA。
● Signal processing
16-bit A/D sampling;Sampling rate: 3000 samples /S。Output true valid value。Data update cycle: configurable;The value ranges from 67mS to 1.7S, the factory default set update time is 1.44S;Overload capacity: 1.2 times the range can be correctly measured;Overload 2x range input 1s is not damaged。Isolation: Isolation between signal input and communication interface output, isolation voltage 1000V DC。DATA+, DATA-, VCC, and GND are the output terminals, and the common ground is the GND terminal. The AGND terminal is the common ground of the 12 signal inputs。
● Communication output
Interface: RS-485 interface, two-wire system, ±15KV ESD protection。
Protocol: MOSBUS-RTU, ASCII code, hexadecimal LC-02 protocol 3 can be selected through the "Parameter setting software" provided by Litron;
Speed: 1200, 2400, 4800, 9600, 19200 Bps, can be set by software。
Module address: 00 ~ FF can be set by software。
Product parameter
● Measurement accuracy:0.Level 2;(Input is 50Hz or DC signal)
● Module power supply:+8 ~ 24V DC * Power consumption: Typical current consumption is 45 mA。
● Working environment:工作温度:-20℃~70℃; 存储温度:-40℃~85℃; 相对湿度:-5%~95%不结露。
● Installation method:DIN rail clamping volume: 122mm *70mm * 43mm。